A DC surge protection device (SPD) for a solar array must be rated above the highest voltage the string can ever produce. That is the open circuit voltage on a cold, bright morning: solar panels give more voltage the colder they are, and on the Highveld a winter dawn below freezing can push a string well above its datasheet figure.
How it works
String voltage at standard conditions. Voc string = panels per string x Voc of one panel (at 25 °C).
On the coldest morning. Voc(T) = Voc string x [1 + β / 100 x (T minus 25)], where β is the panel's temperature coefficient of Voc in percent per degree (a negative number, often about minus 0.25 to minus 0.30 for current panels) and T the lowest cell temperature, taken as the lowest air temperature at dawn.
The SPD rating. A common rule for PV SPDs is a maximum continuous DC voltage UCPV of at least 1.2 times the string's Voc at standard conditions. The calculator also checks the cold morning figure and picks the next common rating above the higher of the two: 600, 800, 1,000, 1,200 or 1,500 V DC.
Type 1 or type 2?
If the building has an external lightning protection system, or the array is exposed and could take a direct strike, the DC side usually gets a type 1 (or combined type 1+2) device. Otherwise type 2 is common. Fit SPDs at the inverter end of each string and, for long cable runs of more than about 10 m, at the array end too, with AC surge protection on the inverter's output and at the DB. See DC surge protection and solar panel lightning protection.
Frequently asked questions
Where do I find the temperature coefficient?
What lowest temperature should I use?
Does the inverter limit matter too?
Sources
- IEC 61643-32: Surge protective devices connected to the DC side of photovoltaic installations, selection and application
- IEC 62548: Photovoltaic arrays, design requirements (cold temperature Voc)
Formulas and table values as published in these standards and papers. The calculators simplify them for a first look; a designer applies the full method.
More calculators
- Lightning risk calculatorCollection area, strikes a year and a suggested protection level (IEC 62305)
- Rolling sphere and air rod calculatorHow far an air rod or mast protects at each height, plus mesh and down conductors
- Separation distance calculatorHow far a down conductor or mast must stay from metal and wiring (IEC 62305-3)
- Earth spike resistance calculatorResistance of one or more earth rods in your soil, and how many reach 10 ohms
- Thunder distance timerCount from flash to bang to see how far the storm is, and when to go inside