Every down conductor ends in an earth electrode, and the lower its resistance, the more easily the strike current spreads into the ground. IEC 62305-3 recommends a low resistance, under 10 ohms where possible, for the common type A arrangement of rods at each down conductor. Soil is the biggest variable: the same spike can read 20 ohms in wet clay and several hundred in dry sand or on rock.
The formulas
One rod. R = ρ / (2πL) x [ln(8L / d) minus 1], where ρ is the soil resistivity in ohm metres, L the driven length in metres and d the rod diameter in metres. This is the Dwight formula used in BS 7430 and IEEE 142.
Rods in a row. Rods close together share the same soil, so two rods are not half the resistance of one. BS 7430 gives Rn = R1 x (1 + λα) / n, with α = ρ / (2π R1 s) for a spacing s, and λ from 1.00 for two rods to 3.81 for ten in a straight line. The rule of thumb is to space rods at least as far apart as they are long.
Typical soil resistivity
The presets use typical values: clay and loam about 50 ohm metres, sandy clay about 150, sand and gravel about 500, dry sand about 1,500 and rock or weathered granite about 3,000. Real soil varies with depth, moisture and season, and Highveld soils dry out in winter. For a design, measure the resistivity on site with a four-pole (Wenner) test and test the finished electrodes. See earth resistance testing.
When rods are not enough
On rock or very dry sand, adding rods quickly stops helping. Installers then use deeper driven rods, a ring earth electrode (a buried conductor around the building, type B), earth enhancing compound, or a combination. Ask your installer which they propose, and see earth spikes, earthing materials and earthing installation.
Frequently asked questions
Is 10 ohms a legal requirement?
Why doesn't doubling the rods halve the resistance?
How accurate is the calculator?
Sources
- BS 7430: Code of practice for protective earthing of electrical installations
- IEEE 142: Recommended Practice for Grounding of Industrial and Commercial Power Systems
Formulas and table values as published in these standards and papers. The calculators simplify them for a first look; a designer applies the full method.
More calculators
- Lightning risk calculatorCollection area, strikes a year and a suggested protection level (IEC 62305)
- Rolling sphere and air rod calculatorHow far an air rod or mast protects at each height, plus mesh and down conductors
- Separation distance calculatorHow far a down conductor or mast must stay from metal and wiring (IEC 62305-3)
- Solar DC surge protector calculatorString voltage on a cold morning and the DC surge device rating to ask for
- Thunder distance timerCount from flash to bang to see how far the storm is, and when to go inside