Separation distance calculator: how far from the wiring and metalwork?

When lightning runs down a conductor, it can jump to nearby wiring, pipes or metal. Enter the protection class, how many down conductors share the current, the material in between and the length of the conductor, and get the minimum distance to keep.

Separation distance calculatorHow far a down conductor or mast must stay from metal and wiring (IEC 62305-3)
Sheet
SDC-01
Method
s = ki kc l / km

The figures update as you type. A guide for planning and briefing, not a design.

Drawing

ki
-
kc
-
km
-
Minimum separation distance s
-

A lightning current of tens of thousands of amps produces a large voltage along a down conductor. Metal parts and cables close to it can flash over, which starts fires and sends the surge into the building. IEC 62305-3 avoids this with a separation distance: either keep everything at least that far away, or bond it to the lightning protection system.

The formula

s = ki x (kc / km) x l, in metres.

  • ki depends on the protection class: 0.08 for class I, 0.06 for II and 0.04 for III and IV.
  • kc is the share of the current in the conductor: 1 with a single down conductor (an isolated mast, for example), 0.66 with two, and 0.44 with three or more connected by a ring at roof level.
  • km depends on what is between the conductor and the metal part: 1 for air and 0.5 for concrete, brick, wood or other solid material. Solid material needs twice the distance.
  • l is the length along the conductor from the point where the distance is checked down to the nearest equipotential bonding point (usually the earth).

Where it matters most

Thatch. An isolated mast or catenary must keep its conductors clear of the thatch and of any wiring, gutters or metal in the roof. Solar arrays. Panel frames and DC cables near air rods or down conductors either stay outside the separation distance or are bonded, with surge protection on the DC side. Rooftop plant and aerials. Air conditioners, satellite dishes and metal handrails close to the conductor are bonded, or the conductor is rerouted. See thatch roof protection and solar panel protection.

Frequently asked questions

What if I can't keep the distance?
Bond the metal part to the lightning protection system at that point, so there is no voltage between them to flash over, and fit surge protection on any cables that are bonded. Where bonding is not acceptable, as with thatch, the conductor or mast has to move further away.
Why is the length measured to the bonding point?
The voltage that drives a flashover builds up along the conductor from the point where everything is tied together. The further up the building, the longer the conductor and the bigger the distance needed. Ring conductors and bonding at each floor shorten it.
Is this the distance from a thatched roof?
It is the electrical minimum for flashover. Thatch is also a fire risk, so SANS 10313 and installers keep masts and conductors well away from the thatch. Ask the installer what distance their design uses and why.

Sources

Formulas and table values as published in these standards and papers. The calculators simplify them for a first look; a designer applies the full method.

More calculators

Free quote request, no obligation

Request quotes for lightning protection for a thatched roof

Fill in the survey sheet the way an installer would on a first visit: the size and height of the building, the roof and the protection class if you know it, or simply how many arresters, plugs, spikes, metres or visits. Installers and suppliers in your area quote you directly.

Site survey sheetThatch Roof Lightning Protection
Sheet
28466
Date
2026-11-21
Scale
NTS

1The job

2The building (optional, it helps the quote)

Elevation with the rolling spherenot to scale

-
-
-
-
-
-
Estimate
-

Geometry and the standard's table figures for the request, not a design.

3Where you are now

4Your list (optional)

  1. 01
  2. 02
Up to 12 lines: rods, masts, arresters, spikes, tape or services.
Needs and options

5Your details

Free and no obligation. By sending you agree that we may share your request with suitable installers, electricians, engineers and suppliers. See our privacy policy.

Get free lightning protection quotes