The rolling sphere method is how lightning protection designers decide where air terminals go. Imagine a sphere rolled over and around the building: anywhere the sphere can touch can be struck and needs an air terminal; anything the sphere cannot reach is protected. The sphere's radius depends on the lightning protection level: 20 m for class I, 30 m for II, 45 m for III and 60 m for IV.
How the zone is worked out
For a single vertical rod or mast of height h, the sphere of radius R rests on the tip and on the ground. Its centre sits at height R, a horizontal distance of √(h(2R minus h)) from the rod. Everything under the curve of the sphere is protected. At a height y above the ground the protected radius is r(y) = √(h(2R minus h)) minus √(y(2R minus y)). If the rod is taller than the sphere radius, only the bottom R metres count, and the side of a very tall mast can itself be struck.
That is why a mast for a thatched house stands well clear of the roof and is tall enough that the whole thatch, including the ridge and the chimney, sits inside the curve. The calculator draws the curve and shows a building of your chosen height and distance under it.
Mesh and down conductors
On flat and low pitched roofs, designers often use a mesh of conductors instead of, or as well as, air rods. IEC 62305-3 gives the maximum mesh size for each class: 5 x 5 m for I, 10 x 10 m for II, 15 x 15 m for III and 20 x 20 m for IV. Down conductors are spaced around the perimeter at typical distances of 10 m for classes I and II, 15 m for III and 20 m for IV, with at least two on any building, each ending in an earth electrode with a test joint.
Using the result
The numbers here are a starting point for a conversation with a designer, not a design. Real roofs have ridges, chimneys, aerials, solar arrays, parapets and plant, each of which the sphere must be rolled over, and isolated systems for thatch also need the right separation distance (see the separation distance calculator). Ask for a layout drawing to SANS 62305-3, and see lightning rods, lightning masts and down conductors.
Frequently asked questions
Does a taller rod always protect more?
Which class should I pick?
What about the protection angle method?
Sources
Formulas and table values as published in these standards and papers. The calculators simplify them for a first look; a designer applies the full method.
More calculators
- Lightning risk calculatorCollection area, strikes a year and a suggested protection level (IEC 62305)
- Separation distance calculatorHow far a down conductor or mast must stay from metal and wiring (IEC 62305-3)
- Earth spike resistance calculatorResistance of one or more earth rods in your soil, and how many reach 10 ohms
- Solar DC surge protector calculatorString voltage on a cold morning and the DC surge device rating to ask for
- Thunder distance timerCount from flash to bang to see how far the storm is, and when to go inside