Lightning protection calculators

Work out how often a building is likely to be struck, what an air rod or mast protects, how far conductors must stay from wiring, how many earth spikes your soil needs, which DC surge device suits a solar string and how far away a storm is.

Six calculatorsLP-TOO-782

Risk
Strikes a year, suggested level
Air rods
Rolling sphere zone, mesh, down conductors
Separation
Distance from metal and wiring
Earthing
Rods for 10 ohms in your soil
Solar
DC SPD voltage rating

Lightning protection is engineering: sphere radii, collection areas, ohms and volts. These free tools put the main numbers in front of you before you ask LightningProtection.co.za for quotes, so you know what to ask for and can compare what comes back.

The calculators

Lightning protection levels at a glance

Every design starts by choosing a protection level, I to IV, usually from a risk assessment. The level sets the rolling sphere, the roof mesh, how far apart the down conductors go and the factor used for separation distances. Level I intercepts more of the smaller strikes, which is why it needs the tighter sphere and mesh.

Lightning protection levels, IEC 62305-1 and 62305-3
LevelRolling sphereMeshDown conductor spacingkiPeak current designed forSmallest strike interceptedStrikes intercepted
I20 m5 x 5 m10 m0.08200 kA3 kA99%
II30 m10 x 10 m10 m0.06150 kA5 kA97%
III45 m15 x 15 m15 m0.04100 kA10 kA91%
IV60 m20 x 20 m20 m0.04100 kA16 kA84%

Lightning in South Africa

The South African Weather Service's lightning detection network has recorded ground flash densities of about 10 to 15 flashes per square kilometre a year over the Highveld and the eastern escarpment, and more than 20 in places along the northern escarpment. Activity falls away towards the west of the country, so the Western Cape sees a small fraction of the strikes Gauteng does. Most storms arrive in the summer rainfall months, from October to March, often in the afternoon.

Frequently asked questions

Are these calculators a substitute for a design?
No. They use the formulas and tables from IEC 62305, BS 7430 and the PV surge protection standards in a simplified form, so you can understand the numbers, check a proposal and brief an installer. A system still needs a design, an installation and a test by people who do this work.
Which standards apply in South Africa?
SANS 62305 parts 1 to 4 (the local adoption of IEC 62305) for risk, the external system, and electrical and electronic systems; SANS 10313 for lightning protection of structures, often quoted for thatch; and SANS 10142-1 for the electrical installation, including surge protection at the board.

Free quote request, no obligation

Request lightning protection quotes

Fill in the survey sheet the way an installer would on a first visit: the size and height of the building, the roof and the protection class if you know it, or simply how many arresters, plugs, spikes, metres or visits. Installers and suppliers in your area quote you directly.

Site survey sheetLightning Protection
Sheet
50329
Date
2026-11-21
Scale
NTS

1The job

2The building (optional, it helps the quote)

Elevation with the rolling spherenot to scale

-
-
-
-
-
-
Estimate
-

Geometry and the standard's table figures for the request, not a design.

3Where you are now

4Your list (optional)

  1. 01
  2. 02
Up to 12 lines: rods, masts, arresters, spikes, tape or services.
Needs and options

5Your details

Free and no obligation. By sending you agree that we may share your request with suitable installers, electricians, engineers and suppliers. See our privacy policy.

Get free lightning protection quotes